Interrupted Electronic Oil Primary  
The new R7184 features interrupted ignition and valve-on delay with selectable  
blower-off delay timings on selected models.  
FEATURES  
Oil-resistant plastic cover for electronics.  
Compatible with hydronic and forced air applications.  
Mounts on standard 4 in. by 4 in. junction box, directly  
Patented cad cell resistance readout.  
on main burner or inside appliance cabinet.  
Available in 15- and 30-second lockout times.  
UL Component Recognition.  
Safe start check.  
CUL Component Recognition.  
Status indicator light monitors burner flame status and  
system lockout.  
Uses proven flame detection and monitoring systems.  
Optional valve-on delay, blower-off delay models.  
– 15 second or selectable 0 or 15 second valve-on  
delay.  
– Zero time or selectable 0-, 2-, 4-, 6-minute blower-off  
delay.  
– Oil valve control.  
– Compatible with power venters without integral  
timers.  
Copyright © 1999 Honeywell Inc.  
All Rights Reserved  
 
68-3033  
L1  
(HOT)  
R7184  
L1  
T8600  
JUMPER  
T
T
FAN RELAY  
LINE VOLTAGE  
THERMOSTAT  
OR AQUASTAT  
CONTROL  
L2  
1
L1  
(HOT)  
RC  
1
®
LIMIT  
COOLING  
G
Y
TRANSFORMER  
L2  
L2  
R
W
COOLING  
CONTROL  
R7184  
L1  
T
1
L1  
LIMIT  
LIMIT  
BURNER  
MOTOR  
BURNER  
MOTOR  
T
(HOT)  
L2  
L2  
IGNITOR  
IGNITOR  
CAD  
CELL  
ALARM  
2
CAD CELL  
VALVE  
OIL VALVE  
JUNCTION BOX  
BURNER  
MOTOR  
BURNER  
MOTOR  
1/4 IN. QUICK CONNECT TERMINAL  
SCREW TERMINAL  
LEGEND:  
IGNITOR  
IGNITOR  
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS  
AND OVERLOAD PROTECTION AS REQUIRED.  
CAD  
CELL  
ALARM  
M16298  
2
CAD CELL  
OPTIONAL FEATURE ON SELECT MODELS.  
Fig. 2. Typical connection for line voltage thermostat and  
R7184A for oil burner system.  
JUNCTION BOX  
1/4 IN. QUICK CONNECT TERMINAL  
SCREW TERMINAL  
LEGEND:  
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS  
AND OVERLOAD PROTECTION AS REQUIRED.  
L1  
(HOT)  
T8600  
FAN RELAY  
M16300  
L2  
OPTIONAL FEATURE ON SELECT MODELS.  
1
RC  
G
COOLING  
TRANSFORMER  
Fig. 4. Typical connection for 24 Vac thermostat  
and R7184B,P,U for valve-on delay/blower-off  
delay oil burner system.  
Y
COOLING  
CONTROL  
R
W
R7184  
T
T
1
L1  
L1  
LIMIT  
(HOT)  
L2  
L2  
BURNER  
MOTOR  
BURNER  
MOTOR  
IGNITOR  
IGNITOR  
CAD  
CELL  
ALARM  
2
CAD CELL  
JUNCTION BOX  
1/4 IN. QUICK CONNECT TERMINAL  
SCREW TERMINAL  
LEGEND:  
1
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS  
AND OVERLOAD PROTECTION AS REQUIRED.  
OPTIONAL FEATURE ON SELECT MODELS.  
M16299  
Fig. 3. Typical connection for 24 Vac thermostat and  
R7184A for oil burner system.  
68-3033  
3
 
Home and Building Control  
Honeywell Inc.  
Honeywell Plaza  
Home and Building Control  
Honeywell Limited-Honeywell Limitée  
155 Gordon Baker Road  
North York, Ontario  
P.O. Box 524  
M2H 3N7  
Minneapolis, MN 55408-0524  
Printed in U.S.A. on recycled  
paper containing at least 10%  
68-3033 G.R. 1-99  
post-consumer paper fibers.  
 

Graham Field Personal Lift US0208 User Manual
Grizzly Sander G1071 User Manual
Grizzly Saw G8976 User Manual
Halo Lighting System Indoor Furnishings L994 User Manual
Hamilton Beach Blender 70610C User Manual
HANNspree Flat Panel Television ST54 10A1 User Manual
Healthrider Treadmill HRTL16900 User Manual
Honeywell Thermostat CT3100 User Manual
Honeywell Thermostat TL8100 User Manual
Humax Satellite TV System F2 FOX User Manual