Ei Electronics Smoke Alarm Ei 407 User Manual

4. Next remove the white element by lifting  
the lower edge (see figure 3).  
(However, this could result in problems  
with nearby systems if their units are  
being house coded at the same time. If  
this is the case remove the MCP from its  
mounting box and then from house code  
mode by pressing and holding the code  
button until the red light comes on (i.e.  
use the same method as to enter house  
code mode). Release the button and the  
red light will go out, indicating that the  
MCP has exited house code mode. Re-  
assemble and attach to box as described  
above.  
Model: Ei 407  
5. Connect the built-in battery by sliding the  
battery switch into the “on” position. (see  
figure 4).  
Manual Call Point  
For use with RadioLINK range of smoke/heat alarms and bases  
6. Press the house code switch until the light  
on the front turns on red (see figure 4). (The  
unit will now send out a coded alarm signal  
and the red light will flash).  
Figure 1  
Figure 6  
7. Screw the front plate to the wall box using the  
two machine screws provided (see figure 5).  
8. Now re-install the white element, yellow  
edge uppermost (see figure 6). Replace the  
bottom housing by lining up the two notches  
and carefully pushing it on - this should  
leave it about 10mm below the bottom edge.  
Please note that this will cause the MCP  
to send out a coded alarm signal which  
will activate the RadioLINK smoke alarms  
and RadioLINK bases that have previous-  
ly been housecoded during the above  
installation procedure).  
Now push the cover bottom firmly against  
the back and slide upwards (see figure 7).  
This resets the switch. The yellow edge on  
the white element should now be hidden.  
(The unit will now send out a coded alarm  
cancel signal). The red light will then  
continue to flash to show it is in house code  
mode, for the next 15 minutes.  
Figure 2  
Figure 7  
3. CHECKING & TESTING THE MCP  
Contains vital information on the products operation and installation.  
Read and retain carefully. If you are just installing this product the  
manual MUST be given to the householder.  
The MCP is an important alarm device and should be tested after  
installation and then weekly (and after prolonged absence) to ensure  
correct operation as follows.  
1. INTRODUCTION  
9. Immediately put all other Radiolink smoke  
alarms and other components into house  
code mode within this 15 minutes .  
Pressing on the Ei407 Manual Call Point (MCP) black spot causes all  
the RadioLINK Alarms to sound. This informs the occupants that the  
building must be evacuated.  
a) Check that the light flashes green every 40 seconds to show it has  
power.  
10. In house code mode, the MCP will now  
send a radio message every 5 seconds. All  
RadioLINK smoke/heat alarms within range  
that are also in house code mode themselves  
will memorise the house code of the MCP.  
Figure 3  
b) Press the black spot and the white element will drop down expos-  
ing the yellow edge to show it is activated. The light will turn red and  
stay on continuously for 3 seconds and then continue to flash red  
(every 20 seconds) for 5 minutes indicating transmission of the alarm  
signal. (Note: after 5 minutes the RF alarm signal ceases and  
therefore the smoke alarms will stop alarming. This prevents the  
batteries in the MCP and the alarm from being depleted).  
The Ei 407 MCP also provides a means to test the RadioLink alarms  
without having to reach up to the smoke alarms on the ceilings as it  
can be reset with the plastic key (supplied).  
BATTERY  
ON/OFF SWITCH  
We suggest that the plastic key is mounted on a small nail under or  
alongside the MCP for future use when resetting (as shown above).  
11. Check that the number of blue light  
flashes (for RadioLINK Smoke Alarms) or  
amber light flashes (for RadioLINK Bases)  
correspond with the number of units in the  
system (e.g. Smoke Alarms plus MCP). For  
example, with 3 RadioLINK Smoke Alarms  
and one MCP you should see 4 blue light  
flashes from each alarm.  
2. INSTALLATION  
c) Check the RadioLink units are now in alarm (If some or all of the  
alarms have not been activated, then the house coding procedure  
should be repeated. If there are still some problems, see the section  
on “Troubleshooting”.)  
It is recommended that you install all the other RadioLINK Smoke  
Alarms and any other RF components before installing this MCP.  
All RadioLINK units should be located in their final positions before  
house coding commences.  
d) The MCP should be reset with the plastic key provided by pushing  
the forked end (arrow side up) into the slots (see figure 1) and pulling  
the bottom housing down. Remove the plastic key. Now push the bot-  
tom housing firmly against the back and slide upwards. This resets the  
switch. The yellow strip on the white element should now be hidden.  
(Note: the MCP flashing red light does not  
indicate the number of units in the system. It  
just flashes rapidly to show it is in house  
code mode. The MCP is only an RF trans-  
mitter and does not receive any RF signals).  
House Code Button  
Figure 4  
1. The MCP should be positioned (approx) 1.2 meters high on a wall, in  
a suitable location on an exit route. (Avoid locating near metal objects).  
2. Securely attach the mounting box to the wall using the fixing  
screws supplied.  
e) If the MCP is not reset the light will flash red every 40 seconds to  
remind the user to reset it.  
12. Remove all the RadioLINK Smoke  
alarms and RadioLINK Bases from house  
code mode as described in their instruction  
leaflets.  
3. Remove the bottom housing by first pushing in the forked end of  
the key (with arrow side out) into the two slots (see figure 1). The  
bottom housing should drop down by about 10mm and expose the  
yellow edge on the white element (with the black spot). Remove the  
key, pull the bottom housing down and then lift it up to remove (see  
figure 2).  
On reset, the alarm cancel signal will be transmitted (indicated by a  
single red light flash for 3 seconds).  
If the light flashes amber every 9 seconds this indicates that the  
batteries are depleted and the MCP will no longer be able to send an  
alarm signal. The unit must be removed from its location and returned  
for repair if under the guarantee period, see section 7 & 8 for details).  
3
13. The MCP will exit the house code mode  
by itself after approx. 15 minutes without  
further user intervention.  
Figure 5  
1
2
 

Echo Trimmer 99944200485 User Manual
Eizo Computer Monitor RX320 User Manual
Everpure Water System SC10 11 User Manual
Exido Hot Beverage Maker 245 065 User Manual
Frigidaire Air Conditioner FRS093LC1 User Manual
Fujitsu VCR M2488 User Manual
Furuno Marine RADAR FCR 902 User Manual
Gaggenau Electric Steamer VK230610 User Manual
GE Washer Dryer commercial washer User Manual
Global Machinery Company Impact Driver IW1000 User Manual